物理代写 Question 1: Total General Lighting and Receptacle Load
General lighting load = 3,800 Sq. ft. x 3 VA = 11400 VA
Small…
Question 1: Total General Lighting and Receptacle Load
General lighting load = 3,800 Sq. ft. x 3 VA = 11400 VA
Small-appliance branch circuit load = 3 Appliance Circuits x 1500 VA = 4500 VA
Laundry branch circuit load. = 1 Laundry Circuit x 1500 VA= 1500 VA
Total General Lighting and Receptacle Load = 11400 + 4500 + 1500 = 17,400 VA
Applying demand factors to the general lighting load.
First 3000 VA at 100% = 3000 VA
Remainder at 35% = (17,400 – 3,000) x 0.35 = 5040 VA
TOTAL General Lighting and Receptacle Load = 3000 + 5040 = 8040 VA
Question 2: Fixed-in-Place Appliance Load Graded Project代写
Water heater 28 kVA = 28000 VA
Dishwasher =1,200 VA
Food Disposal =1,200 VA
Attic Fans =1,500 VA
Total =31,900 VA
75% of total; for 4 or more appliances = 0.75 x31900 = 23,925 VA
Question 3: Dryer Load
Clothes Dryer: 5 Kw = 5000VA
Question 4: Cooking Equipment Demand Load
12kw demand factor is 80%
Equipment demand load = 12 x 0.8 = 9.6 kW = 9600 VA
Question 5: HVAC Load Determine the total AC loads for the HVAC system in this residence.
3.5 Ton AC system 240 V, 17.9 , Air handler 3.3 A
Load due to AC system = V x Iac
=240 x 17.9
=4296 VA
Load due to air handler = V x Iac
=240 x 3.3
= 792 VA
Total HVAC load =4296 + 792
=5088 VA
Question 6: Largest Motor Load Determine the largest motor load for this residence. 物理代考
For the largest motor take food disposal volt-amps x 25% = 1200 x 0.25 = 300 VA
Question 7: Total Demand, Service Size and Service Conductors Based on your calculations for questions 1–6, determine the total demand in VA for this residence, the minimum service size, and the minimum conductor sizes (THW) for the ungrounded and grounding electrode conductors (assume the neutral conductor to be the same as the ungrounded conductor).
TOTAL Volt-Amp Demand Load: = 23,925+5000+9600+5088+300 = 43913 VA
Min. Amperes for service = Total VA / voltage = 43913/240 =182.97 a
Min. Size for service conductors/feeders. NEC 240-6. Use next standard size fuse or breaker = 200 A
Size of service and/or feeder conductors. Use NEC 310-15(b) for the service conductors up to 400 A
Rating > 400 amps min. Size of conductors= 3/0 cu or 250 kcmil al
Min. Size of neutral conductor = no. 2 cu
Size of grounding electrode conductor 200 amp service with 3/0 service conductors, the size = 4 cu
Question 8: Which article of the NEC describes the proper placement of outlets in this type of room?
Article 210.
Question 9: Part 1: According to the NEC, what is the maximum wall space that’s allowed between two adjacent outlets?
12 feet.
Part 2: How large must a wall space be to require an outlet?物理学代写
2 feet
Part 3: Should an outlet located at 7-feet up the wall from the floor, used to power a light fixture, be included in wall space requirement?
YES
Question 10: If the outlets in this room are supplied by a single 15A or 20A circuit, what is the maximum current that can be supplied (in amps) to a cord-and plug connected load? 物理学代写
20 Amps and not more than 125% of the load
Question 11: Look at the items listed in Table 1. Indicate which items are considered to be wall space by the NEC, and which items aren’t considered to be wall space. (Place an “X” in the appropriate column next to each item.
Table 1 | ||
Item |
Considered to Be Wall Space |
Not Considered to Be Wall Space |
Fireplace | X | |
Fixed glass panel | X | |
Sliding segment of glass door | X | |
Door opening | X | |
Bar-type counter | X | |
Wall space less than 1 foot wide | X | |
Wall space 3 feet wide | X | |
Doorway | X | |
Fixed cabinet | X |
Question 12: Part 1: In Figure 1, note that a switch is located close to the door. This switch operates an overhead light fixture. This arrangement is a requirement of the NEC. Which article of the NEC covers this regulation for a room of this type? Graded Project代写
Article 210
Part 2: Other than the switch shown in Figure 1, what alternative way can be used to meet the NEC
requirement?
No other way
Question 13: If the branch circuits supplying the receptacles in the figure are rated at 20 A, what is the minimum ampacity rating of the conductors in the branch circuit?
3.1 Amp or Lower
Question 14: How many branch circuits that supply the room shown in Figure 1 are required to be GFCI protected according to the NEC? Graded Project代写
= 4
Question 15: What section of the NEC covers the use of GFCI-protected outlets in a residential kitchen?
Article 210.8
Question 16: How many of the outlets shown in Figure 2 are required to be GFCI protected by the NEC? Identify the location of the outlets you selected on the figure.
7 Along cabinet and counter
Question 18: The outlets along the countertop are to be used for small appliances. What is the minimum number of branch circuits that would be needed to supply just these
small-appliance outlets?
There is no restriction on the number of branch circuits
Question 19: Part 1: What is the maximum distance (in feet) that the receptacle intended for the refrigerator can be from that appliance? Graded Project代写
2 feet and in place appliances
Part 2: Name two common kitchen appliances that may require receptacle locations to be closer than required by 210.50 due to restrictions on cord lengths?
Electric cooker and Oven
Question 20: What is the minimum circuit protection (in amps) and wire size needed for each of the required small appliance circuits?
38 Amp wire size would be 12
Question 21: In Figure 2, note that an electrical outlet is shown on the island in the kitchen area. Is this outlet required by the NEC, or does it represent an NEC violation?
No. It has to be that way.
Question 22: Looking again at the island counter in the kitchen. If the countertop above the outlet was extended 12 inches beyond the base of the cabinet to allow bar-stool seating at the counter, would that change the NEC status of the outlet? . Graded Project代写
No. It is under the same code
Question 23: Suppose that a built-in dishwasher is to be installed in this kitchen. Does the NEC allow the dishwasher to be connected to the existing small-appliance circuits?
No
Question 24: Can any of the receptacles required for the countertop space be mounted in the actual countertop? Cite an NEC section and condition to support your answer.
Yes. Section 210.50
Question 25: Does the NEC allow the lighting circuit for a kitchen to be attached to the small-appliance circuits?
Yes
Question 26: What is the maximum height that the outlets on either side of the sink can be installed above the countertop surface? Graded Project代写
24 to 48 inches
Question 27: If the distance between the outlets on either side of the range in Figure 2 is less than 4 feet, are both outlets required per the NEC? Briefly explain your answer.
No. Due to limited space.
Question 28: What section of the NEC covers the use of GF protected outlets in a residential bathroom?
Section 210.8
Question 29: How many of the outlets shown are required to be GFCI protected by the NEC
All outlets
Question 30: In what situation would the NEC allow any on of the outlets in this bathroom to supply power to an outlet to another room? . Graded Project代写
None
Question 31: The receptacle near the basin in figure can be mounted on the countertop and, if a listed assembly, in the countertop. In what position may the receptacle not be mounted?
Sideways
Question 32: Looking again at the receptacle near the basin What is the maximum distance the outlet can be away from the outside edge of the basin?
2 feet
Question 33: You’re rewiring the bathroom in Figure 3 as part of a remodeling project. The customer requests a GFC receptacle on the back wall of the bathtub area, 5-feet from the top edge of the tub. Should you comply with the custom request? Site an NEC section to support your answer.
No. Section 210.8
Question 34: Does the NEC allow the lighting circuit in the bathroom area to be connected to the same circuit as the outlet receptacles?
No
Question 35: What is the demand load for this circuit? Graded Project代写
240 Volts
Question 36: What size TW copper conductor should be used for the branch circuit?
6 gauge wire.
Question 37: What would be the demand load for this branch circuit?
240 V
Question 38: What is the minimum-size TW copper conductor that should be used for this branch circuit?
6 wire 3-phase
Question 39: What would be the demand load for all of these items? Graded Project代写
4,600 V
Question 40: Review the figures, note all NEC violations in each one, and determine which NEC article has been violated. Use this information to complete the remainder of
TABLE | ||
FIGURE NAME | Description of the NEC violation | NEC article violated |
8 | Outlet not GFCI protected | 210.8 |
9 | Outlet supplied by 15A instead of 20A branch circuit | 210.11 |
10 | Outdoor receptacle not GFCI protected | 210.8 |
11 | Wrong wall space requirement | 210.12 |
12 | Use of 15 A branch on an a outlet | 210.11 |